Skip to main content
Chlorine Measurement - View 1
Liquid Analysis Products / Chlorine Measurement

Chlorine Measurement

This analyser has been designed to monitor Free Chlorine (Residual Chlorine) in drinking water, industrial cooling water, rinse water, wastewater or other fresh water samples containing Chlorine in the range of 0.05-20 ppm (High Range) or 0.01 to 5.00 (Low Range). With its plug-and-play design, our Free Chlorine Analyser includes a pH sensor, a chlorine sensor, a flow control device and a transmitter that is mounted on a PVC panel. It is calibrated at the factory before shipment.

Measurement Range
0.05-20 ppm (Hight Range), 0.01 to 5.00 (Low Range)
Accuracy
(±)2% of calibrated range
Power Supply Options
100 - 240 Vac / 24 Vdc
Analog Output and Digital Communication
Isolated 4-20 mA output and MODBUS® RTU
Contact Relays (Optional)
3 x SPDT relays, can be configured as Alarm (set point) relays, timer activated relays or fault relays.
Transmitter Housing
Polycarbonate
Ingress Protection
NEMA 4X (IP66), Weatherproof
Display
144 mm (H) x 144 mm (W) x 90 mm (D)
Chlorine Sensor
Polarographic, Gold cathode/Silver-Silver chloride anode, PTFE membrane
pH Sensor
Intelligent pH sensor to provide automatic compensation
Sample Requirement
40 - 300 LPH
Sample Pressure
0.1 - 2 Bar
Sample Inlet
¼” NPT(F)
Sample Drain
¾” NPT(F)
CUSTOM CONFIGURATION & APPLICATION SUPPORT

Discuss Your Process Requirements with an AZtec Engineer

Need assistance sizing sample conditioning components, selecting optical sensors, or specifying custom process instrumentation? Our engineering team in New Delhi provides technical consultations for industrial plants across India.